  1.                          SECTION 15831
  2.  
  3.                     AIR CURTAINS, COMMERCIAL
  4. NOTE ** This section is based on products manufactured by
  5.         Mars(R) Air Doors, at the following address:
  6. NOTE **      14716 South Broadway
  7. NOTE **      Gardena CA 90248
  8. NOTE **      Tel: (213) 770-1555
  9. NOTE **      Tel: (800) 421-1266
  10. NOTE **      Fax: (310) 324-3030
  11. NOTE **
  12. NOTE ** Mars Air Doors offers a complete line of Air
  13.         Curtains providing the benefits of temperature
  14.         control and environmental separation.  Models are
  15.         offered in a commercial and industrial design and
  16.         can be configured with heat.  Heated units include
  17.         gas, electric, steam and hot water coil models.
  18.  
  19. NOTE ** A typical installation is over a building's
  20.         exterior door or window opening.  They provide
  21.         excellent protection at reducing a building's
  22.         heating and cooling costs when these exterior doors
  23.         need to be opened.  At the same time, they repel
  24.         gusts of wind and minimize the entrance of
  25.         windborne dust, fumes, pollutants, and flies.
  26.         Additionally, they help to expedite the flow of
  27.         traffic from one work area to another or in and out
  28.         the building, by providing an unobstructive view of
  29.         the opening.  This section covers the commercial
  30.         part of their product line:  "Service Window,"
  31.         "Whispurr Air(R)," "C-CH-CHS," "Combi(R) and
  32.         Super Combi," "Hepac(R)," and National Sanitation
  33.         Foundation (NSF) models.  Commercial models
  34.         configured with heat are available in electric heat
  35.         only.  For other forms of heat, see their other
  36.         Section 15832 for industrial models.
  37. NOTE **
  38. NOTE ** SECTION 15831 - AIR CURTAINS, COMMERCIAL, Copyright
  39.         1998, The Architect's Catalog, Inc.
  40.  
  41. PART 1  GENERAL
  42.  
  43. 1.1 SECTION INCLUDES
  44. NOTE ** Select paragraphs below applicable to project.
  45.  
  46.     A.  Service Window Models.
  47.  
  48.     B.  Whispurr Air(R) Models.
  49.  
  50.     C.  C-CH-CHS Models.
  51.  
  52.     D.  Combi(R) and Super Combi Models.
  53.  
  54.     E.  National Sanitation Foundation (NSF) Models.
  55.  
  56.     F.  High Efficiency Particulate Air Curtain (HEPAC) Models.
  57. NOTE ** The following includes service window, C-CH-CHS
  58.         models only.
  59.  
  60.     G.  Air Curtains with Electric Heat.
  61.  
  62. 1.2 RELATED SECTIONS
  63. NOTE ** Sections listed in the following paragraphs
  64.         represent those most likely to relate to this
  65.         section; coordinate with other sections, delete
  66.         those not relevant to this project, add others as
  67.         required.
  68.  
  69.     A.  Section 08110 - Steel Doors and Frames.
  70.  
  71.     B.  Section 08330 - Coiling Doors and Grilles.
  72.  
  73.     C.  Section 08400 - Entrances and Storefronts.
  74.  
  75.     D.  Section 08500 - Windows.
  76.  
  77.     E.  Section 08580 - Pass Windows.
  78.  
  79.     F.  Sections of Division 16 affecting, or affected by,
  80.         construction activities of this section.
  81.  
  82. 1.3 SUBMITTALS
  83.  
  84.     A.  Submit under provisions of Section 01300.
  85.  
  86.     B.  Product Data:  Manufacturer's descriptive literature for
  87.         products specified in this section; indicate options
  88.         specified.
  89.  
  90.     C.  Shop Drawings:  Indicate installation and connection
  91.         details for air curtains.
  92.  
  93.     D.  Quality Assurance Submittals:
  94.         1.  Certificates:  Indicate compliance to Regulatory
  95.             Requirements specified in QUALITY ASSURANCE Article
  96.             of this section.
  97.         2.  Manufacturer's instructions:  Printed installation
  98.             instructions for each specified product.
  99.  
  100.     E.  Closeout Submittals:
  101.         1.  Operation and maintenance data:  Manufacturer's
  102.             printed instructions for operating and maintaining
  103.             air curtain components.
  104.         2.  Warranty documents:  Issued and executed by
  105.             manufacturer.
  106.  
  107. 1.4 QUALITY ASSURANCE
  108.  
  109.     A.  Manufacturer Qualifications:  Minimum five years
  110.         documented experience producing respective products
  111.         specified in this Section.
  112. NOTE ** Delete agency certifications below not required for
  113.         project.
  114.  
  115.     B.  Regulatory Requirements:  Product compliance with the
  116.         following regulatory agencies:
  117.         1.  Underwriters Laboratories.
  118.         2.  National Sanitation Foundation (NSF models only).
  119.         3.  National Electrical Code.
  120.         4.  United States Food and Drug Administration.
  121.         5.  United States Department of Agriculture.
  122.  
  123. 1.5 DELIVERY, STORAGE, AND HANDLING
  124.  
  125.     A.  Store products of this section in manufacturer's unopened
  126.         packaging until installation.
  127.  
  128.     B.  Maintain dry, heated storage area for products of this
  129.         section until installation of products.
  130.  
  131. 1.6 WARRANTY
  132.  
  133.     A.  Supply manufacturer's standard warranty against defects
  134.         in product workmanship and materials.
  135.  
  136.  
  137. PART 2  PRODUCTS
  138.  
  139. 2.1 MANUFACTURERS
  140.  
  141.     A.  Acceptable Manufacturer:  Mars Air Doors, 14716 South
  142.         Broadway, Gardena CA 90248; ASD. Tel: (213) 770-1555 or
  143.         (800) 421-1266; Fax: (310) 324-3030.
  144. NOTE ** Delete one of the two following paragraphs;
  145.         coordinate with Division 01 requirements.
  146.  
  147.     B.  Requests for substitutions will be considered in
  148.         accordance with provisions of Section 01600.
  149.  
  150.     C.  Substitutions:  Not permitted.
  151.  
  152. 2.2 MANUFACTURED UNITS
  153. NOTE ** Retain following paragraph if specifying Mars Model
  154.         Number W-25 service window air curtains.  Model W-
  155.         25 provides protection from insects, dust, and
  156.         fumes; available heated or unheated.
  157. NOTE **
  158. NOTE ** The housing will not crack, chip, fade, or peel,
  159.         and is impervious to high humidity and all climatic
  160.         conditions.
  161.  
  162.     A.  Service Window Air Curtains:
  163.         1.  Acceptable Product:  Mars Model Number W-25.
  164.         2.  Product Description:  Self-contained electrically-
  165.             operated air curtain for mounting at head or jamb of
  166.             openings up to 60 inches (1,524 mm) high by 30 inches
  167.             (762 mm) wide.
  168.         3.  Housing:  One piece molded high impact white
  169.             polyethylene material; resistant to high humidity and
  170.             all climatic conditions.  Contains factory-provided
  171.             mounting brackets at each end, and removable,
  172.             washable aluminum mesh air intake filter.
  173. NOTE ** Delete one of the following two paragraphs.
  174.         Variable-speed fan assembly in the first paragraph
  175.         is available on heated models only.
  176.         4.  Fan Assembly:  Variable-speed, double-shaft motor
  177.             with dual inlet fans having capacity to provide 1,400
  178.             feet per minute (7 m/sec) air velocity and 1,900
  179.             cubic feet per minute (897 L/sec) air volume at
  180.             nozzle, and minimum 600 feet per minute (3 m/sec) air
  181.             velocity at 2 feet (610 mm) above counter when
  182.             mounting height does not exceed 5 feet (1,524 mm)
  183.             above counter.
  184.         5.  Fan Assembly:  Double-shaft motor with dual inlet
  185.             fans having capacity to provide 1,400 feet per minute
  186.             (7 m/sec) air velocity and 1,900 cubic feet per
  187.             minute (897 L/sec) air volume at nozzle, and minimum
  188.             600 feet per minute (3 m/sec) air velocity at 2 feet
  189.             (610 mm) above counter when mounting height does not
  190.             exceed 5 feet (1,524 mm) above counter.
  191. NOTE ** Delete following paragraph if specifying unit
  192.         without heater.
  193.         6.  Heater Assembly:  Electric heater having 4000 watt,
  194.             13,700 BTU (14,454 J) per hour output, with manual-
  195.             reset thermal overload switch and on/off control
  196.             switch.
  197.         7.  Operating Noise Level:  59 decibels on A scale,
  198.             measured from interior, at 10 feet (3.048 m) from
  199.             unit.
  200. NOTE ** Retain one of following three paragraphs; retain
  201.         first or second paragraph if specifying unit
  202.         without heater, retain third paragraph if
  203.         specifying unit with heater.
  204.         8.  Utility Requirements:  115 Volts AC, single-phase,
  205.             2.6 Amperes.
  206.         9.  Utility Requirements:  208/230 Volts AC, single-
  207.             phase, 1.3 Amperes.
  208.         10. Utility Requirements:  208/230 Volts AC, single-
  209.             phase, 22 Amperes.
  210. NOTE ** Retain following paragraph if specifying Mars
  211.         Whispurr Air(R) unit.  These units are 7-1/2 inches
  212.         (190 mm) high, providing a low-profile design for
  213.         restricted ceiling heights.  Installed inside, they
  214.         provide a cost-effective solution for doors in
  215.         continual use or left open for extended periods.
  216.         They can also be used over walk-in cooler/freezer
  217.         doors to reduce cold air loss when door is opened.
  218.  
  219.     B.  Air Curtains:
  220. NOTE ** Insert Model Number information in following
  221.         paragraph.
  222.         1.  Acceptable Product:  Mars Whispurr Air(R) Model
  223.             Number WA-__.
  224.         2.  Product Description:  Self-contained electrically-
  225.             operated air curtain for mounting at head of openings
  226.             up to 7 feet (2.134 m) high by 72 inches (1,829 mm)
  227.             wide.
  228.         3.  Housing:
  229.             a.  One piece molded, high impact, white polyethylene
  230.                 material; resistant to high humidity and all
  231.                 climatic conditions.  Discharge outlet nozzle
  232.                 directional vanes adjustable +/- 20 degrees front
  233.                 to back.
  234.             b.  Mounting plate provided with keyhole slot for
  235.                 fast and easy installation and maintenance
  236. NOTE ** Delete all but one of the following subparagraphs.
  237.         White is production color; custom colors available.
  238.             c.  Color:   White.
  239.             d.  Color:   Gray.
  240.             e.  Color:   Gold.
  241.             f.  Color:   Beige.
  242.             g.  Color:   Dark Bronze.
  243.             h.  Color:   Custom color selected by Architect.
  244. NOTE ** Insert information into following paragraph;
  245.         consult manufacturer's product data for specific
  246.         model specifications.
  247.         4.  Blower Assembly:  Variable-speed motor and switch;
  248.             field adjustable with control knob capable of
  249.             reducing outlet air velocity up to 60 percent.
  250.             Injection molded type blower wheel utilizing
  251.             PolyMars(R) material; capacity to provide 1,800 feet
  252.             per minute (9 m/sec) air velocity and ____ cubic feet
  253.             per minute (____ L/sec) air volume at nozzle.
  254. NOTE ** Retain following paragraph if specifying unit with
  255.         optional door-activated microswitch.
  256.         5.  Door-Activated Microswitch:  Supply microswitch for
  257.             automatic on/off control; turns air curtain on when
  258.             door is opened and off when door is closed; field
  259.             installed.
  260. NOTE ** Delete one of the following two paragraphs.
  261.         Plunger type is for doors with hinges (swing
  262.         doors), roller type for all other types of doors.
  263.             a.  Type:  Plunger.
  264.             b.  Type:  Roller.
  265. NOTE ** Insert information into following paragraph;
  266.         consult manufacturer's product data for specific
  267.         model specifications.
  268.         6.  Operating Noise Level:  __ decibels on A scale,
  269.             measured from interior, 10 feet (3.048 m) from unit.
  270. NOTE ** Insert information into following paragraph;
  271.         consult manufacturer's product data for specific
  272.         model specifications.
  273.         7.  Utility Requirements:  ___ Volts AC, single-phase,
  274.             ___ Ampere.
  275. NOTE ** Retain following paragraph if specifying a Mars
  276.         Unheated C, CH, or CHS unit.  The C Model is
  277.         designed for use over customer entrances, acting as
  278.         a barrier against outside climate.  The CH/CHS
  279.         Models produce greater air velocity with slightly
  280.         higher sound levels and are recommended over
  281.         receiving and service entrance doors at
  282.         restaurants, hospitals, schools, food processing
  283.         plants, etc.  The C, CH, and CHS models are
  284.         effective up to 8 feet (2.438 m), 10 feet (3.048
  285.         m), and 12 feet (3.658 m) high, respectively.
  286.  
  287.     C.  Air Curtains:
  288. NOTE ** Insert Model Number information in following
  289.         paragraph.
  290.         1.  Acceptable Product:  Mars Model Number ____ C__.
  291.         2.  Product Description:  Self-contained electrically-
  292.             operated air curtain for mounting at head of
  293.             openings.
  294.         3.  Housing:
  295.             a.  One piece molded white high-impact polyethylene
  296.                 material, resistant to high humidity and all
  297.                 climatic conditions.
  298.             b.  Internal steel bracket with sufficient strength
  299.                 to provide housing rigidity and fastening to
  300.                 wall.
  301.             c.  Mechanically field adjustable variable air intake
  302.                 louver assembly capable of reducing outlet air
  303.                 velocity up to 60 percent with louvers in totally
  304.                 enclosed position.
  305.             d.  Wedge shaped discharge air outlet nozzle
  306.                 containing adjustable air directional vanes with
  307.                 a +/- 20 degree sweep from front to back.
  308. NOTE ** Delete one of the following two paragraphs. White
  309.         is production color; gold, gray, beige, dark
  310.         bronze, and custom colors are available at a
  311.         nominal charge.
  312.             e.  Color:   White.
  313.             f.  Color:   ______________.
  314. NOTE ** Insert information into following paragraph;
  315.         consult manufacturer's product data for specific
  316.         model specifications.
  317.         4.  Blower Assembly:  Direct-drive, double-width and
  318.             double-inlet squirrel cage steel blower wheels having
  319.             capacity to provide ____ feet per minute (____ m/sec)
  320.             air velocity and ____ cubic feet per minute (____
  321.             L/sec) air volume at nozzle.
  322. NOTE ** Delete three of the following four paragraphs;
  323.         consult manufacturer's product data for specific
  324.         model specifications.
  325.         5.  Motor:  Single 1/2 horsepower, maximum 1,750
  326.             revolutions per minute, single-speed, with two-speed
  327.             option.
  328.         6.  Motor:  Single 1 horsepower, maximum 1,750
  329.             revolutions per minute, single-speed, with two-speed
  330.             option.
  331.         7.  Motor:  Two 1/2 horsepower, maximum 1,750 revolutions
  332.             per minute, single-speed, with two-speed option, both
  333.             controlled by single switch.
  334.         8.  Motor:  Two 1 horsepower, maximum 1,750 revolutions
  335.             per minute, single-speed, with two-speed option, both
  336.             controlled by single switch.
  337. NOTE ** Retain following paragraph if specifying unit with
  338.         optional door-activated microswitch.
  339.         9.  Door-Activated Microswitch:  Supply microswitch for
  340.             automatic on/off control, on when door is opened, off
  341.             when door is closed; field installed.
  342. NOTE ** Delete one of the following two paragraphs.
  343.         Plunger type is for doors with hinges (swing
  344.         doors), roller type for all other types of doors.
  345.             a.  Type:  Plunger.
  346.             b.  Type:  Roller.
  347. NOTE ** Insert information into following paragraph;
  348.         consult manufacturer's product data for specific
  349.         model specifications.
  350.         10. Operating Noise Level:  __ decibels on A scale,
  351.             measured from interior, 10 feet (3.048 m) from unit.
  352. NOTE ** Insert information into following paragraph;
  353.         consult manufacturer's product data for specific
  354.         model specifications.
  355.         11. Utility Requirements:  ___ Volts AC, ______-phase,
  356.             ___ Ampere(s).
  357. NOTE ** Retain following paragraph if specifying Mars
  358.         Heated Model C, CH, or CHS unit.  Heated air
  359.         curtains must be mounted on inside of building.
  360.         They come complete with air curtain, motor control
  361.         panel (factory mounted to air curtain housing) and
  362.         wall mounted thermostat (shipped loose to be field
  363.         installed).  They can be used with fan only in warm
  364.         weather, or with fan and heater in cold weather
  365.         when they will contribute to the building heating
  366.         system.  Heated air curtains should primarily be
  367.         used to reduce the "wind chill" effect of the air
  368.         stream for those walking through it.
  369.  
  370.     D.  Air Curtains with Heater Assemblies:
  371. NOTE ** Insert Model Number information in following
  372.         paragraph; C-1 or C-3, CH-1 or CH-3, CHS-1 or CHS-
  373.         3.
  374.         1.  Acceptable Product:  Mars Model Number Heated___ C__.
  375.         2.  Product Description:  Self-contained electrically-
  376.             operated air curtain for mounting at head of
  377.             openings.
  378.         3.  Housing:
  379.             a.  One piece molded white high-impact polyethylene
  380.                 material, resistant to high humidity and all
  381.                 climatic conditions.
  382.             b.  Internal steel bracket with sufficient strength
  383.                 to provide housing rigidity and fastening to
  384.                 wall.
  385.             c.  Mechanically field adjustable variable air intake
  386.                 louver assembly capable of reducing outlet air
  387.                 velocity up to 60 percent with louvers in totally
  388.                 enclosed position.
  389.             d.  Wedge shaped discharge air outlet nozzle
  390.                 containing adjustable air directional vanes with
  391.                 a +/- 20 degree sweep from front to back.
  392. NOTE ** Delete one of the following two paragraphs. White
  393.         is production color; gold, gray, beige, dark
  394.         bronze, and custom colors are available at a
  395.         nominal charge.
  396.             e.  Color:   White.
  397.             f.  Color:   ______________.
  398. NOTE ** Insert information into following paragraph;
  399.         consult manufacturer's product data for specific
  400.         model specifications.
  401.         4.  Blower Assembly:  Direct-drive, double-width and
  402.             double-inlet squirrel cage steel blower wheels having
  403.             capacity to provide ____ feet per minute (____ m/sec)
  404.             air velocity and ____ cubic feet per minute (____
  405.             L/sec) air volume at nozzle.
  406. NOTE ** Delete three of the following four paragraphs;
  407.         consult manufacturer's product data for specific
  408.         model specifications.
  409.         5.  Motor:  Single 1/2 horsepower, maximum 1,750
  410.             revolutions per minute, single-speed, with two-speed
  411.             option.
  412.         6.  Motor:  Single 1 horsepower, maximum 1,750
  413.             revolutions per minute, single-speed, with two-speed
  414.             option.
  415.         7.  Motor:  Two 1/2 horsepower, maximum 1,750 revolutions
  416.             per minute, single-speed, with two-speed option, both
  417.             controlled by single switch.
  418.         8.  Motor:  Two 1 horsepower, maximum 1,750 revolutions
  419.             per minute, single-speed, with two-speed option, both
  420.             controlled by single switch.
  421. NOTE ** Retain one of the three following paragraphs if
  422.         specifying unit with optional door-activated
  423.         microswitch.
  424.         9.  Door-Activated Microswitch:  Supply microswitch for
  425.             automatic on/off control, on when door is opened, off
  426.             when door is closed; field installed.
  427. NOTE ** Delete one of the following two paragraphs.
  428.         Plunger type is for doors with hinges (swing
  429.         doors), roller type for all other types of doors.
  430.             a.  Type:  Plunger.
  431.             b.  Type:  Roller.
  432. NOTE ** Electric heated units can feature optional delay
  433.         microswitches.  Delay microswitches feature delay
  434.         timers pre-mounted in the control panel.  Delay
  435.         microswitches keep the air curtain running for a
  436.         specified period of time after the door is closed,
  437.         preventing the electric coil from cooling down
  438.         after the door closes, thereby providing the
  439.         necessary heat on demand when the door is re-
  440.         opened.  They are best used when sporadic traffic
  441.         flows through the door opening.  Two types are
  442.         offered; select from the following two paragraphs.
  443.         10. Fixed Delay Microswitch:
  444. NOTE ** Select one of the following paragraphs.
  445.             a.  Delay:  30 seconds, factory preset.
  446.             b.  Delay:  60 seconds, factory preset.
  447.             c.  Delay:  90 seconds, factory preset.
  448.             d.  Delay:  120 seconds, factory preset.
  449.             e.  Delay:  240 seconds, factory preset.
  450.             f.  Delay:  600 seconds, factory preset.
  451. NOTE ** Delete one of the following two paragraphs.
  452.         Plunger type is for doors with hinges (swing
  453.         doors), roller type for all other types of doors.
  454.             g.  Type:  Plunger.
  455.             h.  Type:  Roller.
  456.         11. Adjustable Time Delay Microswitch:  Field adjustable
  457.             to 17 minutes.
  458. NOTE ** Delete one of the following two paragraphs.
  459.         Plunger type is for doors with hinges (swing
  460.         doors), roller type for all other types of doors.
  461.             a.  Type:  Plunger.
  462.             b.  Type:  Roller.
  463. NOTE ** Insert information into following paragraph;
  464.         consult manufacturer's product data for specific
  465.         model specifications.
  466.         12. Operating Noise Level:  __ decibels on A scale,
  467.             measured from interior, 10 feet (3.048 m) from unit.
  468. NOTE ** Insert information into following paragraph;
  469.         consult manufacturer's product data for specific
  470.         model specifications.
  471.         13. Heater Assembly:  Electric heater, ______ watts,
  472.             ______ BTUs (______ J) per hour output, with
  473.             temperature limit controller.
  474.         14. Thermostat:  Wall-mounted, 24-Volt operation, with
  475.             heater on/fan on and heater off/fan on selection.
  476. NOTE ** Insert information into following paragraph;
  477.         consult manufacturer's product data for specific
  478.         model specifications.
  479.         15. Utility Requirements:  ___ Volts AC, ______-phase,
  480.             ___ Ampere(s).
  481. NOTE ** Retain following paragraph if specifying Mars
  482.         COMBI(R) units.  These units are available only
  483.         unheated.  Otherwise, they can be used for the same
  484.         purposes as the C, CH, and CHS models.
  485.  
  486.     E.  Air Curtains:
  487. NOTE ** Insert Model Number information in following
  488.         paragraph.
  489.         1.  Acceptable Product:  Mars Model Number ____ COMBI(R).
  490.         2.  Product Description:  Self-contained electrically-
  491.             operated air curtain for mounting at head of openings
  492.             up to 10 feet (3.048 m) high.
  493.         3.  Housing:
  494.             a.  One piece molded white high-impact polyethylene
  495.                 material, resistant to high humidity and all
  496.                 climatic conditions.
  497.             b.  Internal steel bracket with sufficient strength
  498.                 to provide housing rigidity and fastening to
  499.                 wall.
  500.             c.  Mechanically field adjustable variable air intake
  501.                 louver assembly capable of reducing outlet air
  502.                 velocity up to 60 percent with louvers in totally
  503.                 enclosed position.
  504.             d.  Wedge shaped discharge air outlet nozzle
  505.                 containing adjustable air directional vanes with
  506.                 a +/- 20 degree sweep from front to back.
  507. NOTE ** Delete all but one of the following subparagraphs.
  508.         White is standard; custom colors available.
  509.             e.  Color:   White.
  510.             f.  Color:   Gray.
  511.             g.  Color:   Gold.
  512.             h.  Color:   Beige.
  513.             i.  Color:   Dark Bronze.
  514.             j.  Color:   Custom color selected by Architect.
  515. NOTE ** Insert information into following paragraph;
  516.         consult manufacturer's product data for specific
  517.         model specifications.
  518.         4.  Blower Assembly:  Direct-drive, double-width and
  519.             double-inlet squirrel cage steel blower wheels having
  520.             capacity to provide ____ feet per minute (____ m/sec)
  521.             air velocity and ____ cubic feet per minute (____
  522.             L/sec) air volume at nozzle.
  523. NOTE ** Delete one of the following two paragraphs; consult
  524.         manufacturer's product data for specific model
  525.         specifications.
  526.         5.  Motor:  Single 1/2 horsepower, three-speed, with
  527.             three-speed on/off control switch; single phase only.
  528.         6.  Motor:  Two 1/2 horsepower, three-speed, both
  529.             controlled by single three-speed on/off control
  530.             switch; single phase only.
  531. NOTE ** Retain following paragraph if specifying unit with
  532.         optional door-activated microswitch.
  533.         7.  Door-Activated Microswitch:  Supply microswitch for
  534.             automatic on/off control, on when door is opened, off
  535.             when door is closed; field installed.
  536. NOTE ** Delete one of the following two paragraphs.
  537.         Plunger type is for doors with hinges (swing
  538.         doors), roller type for all other types of doors.
  539.             a.  Type:  Plunger.
  540.             b.  Type:  Roller.
  541. NOTE ** Insert information into following paragraph;
  542.         consult manufacturer's product data for specific
  543.         model specifications.
  544.         8.  Operating Noise Level:  __ decibels on A scale,
  545.             measured from interior, 10 feet (3.048 m) from unit.
  546. NOTE ** Insert information into following paragraph;
  547.         consult manufacturer's product data for specific
  548.         model specifications.
  549.         9.  Utility Requirements:  ___ Volts AC, ______-phase,
  550.             ___ Ampere(s).
  551. NOTE ** Retain following paragraph if specifying Mars Type
  552.         NSF units, available unheated only.  The NCH suffix
  553.         models, for customer entrance doors, utilize one or
  554.         two 1/2-horsepower motors, providing up to 3,400
  555.         FPM (17 m/sec) air velocity at the nozzle and 600
  556.         FPM (3 m/sec) measured 3 feet (0.914 m) off the
  557.         floor.  The NHV prefix models, for receiving doors,
  558.         utilize one 1-horsepower motor, providing up to
  559.         4,600 FPM (23 m/sec) air velocity at the nozzle and
  560.         1,600 FPM (8 m/sec) measured 3 feet (0.914 m) off
  561.         the floor.
  562.  
  563.     F.  National Sanitation Foundation (NSF) Certified Air
  564.         Curtains:
  565. NOTE ** Insert Model Number information in following
  566.         paragraph.
  567.         1.  Acceptable Product:  Mars Model Number ____.
  568.         2.  Product Description:  Self-contained electrically-
  569.             operated air curtain for mounting at head of openings
  570.             up to 12 feet (3.658 m) high.
  571.         3.  Housing:
  572.             a.  One piece molded white high-impact polyethylene
  573.                 material, resistant to high humidity and all
  574.                 climatic conditions.
  575.             b.  Internal steel bracket with sufficient strength
  576.                 to provide housing rigidity and fastening to
  577.                 wall.
  578.             c.  Washable aluminum mesh air intake filter.
  579.             d.  Wedge shaped discharge air outlet nozzle
  580.                 containing adjustable air directional vanes with
  581.                 a +/- 20 degree sweep from front to back.
  582. NOTE ** Delete all but one of the following subparagraphs.
  583.         White is standard; custom colors available.
  584.             e.  Color:   White.
  585.             f.  Color:   Gray.
  586.             g.  Color:   Gold.
  587.             h.  Color:   Beige.
  588.             i.  Color:   Dark Bronze.
  589.             j.  Color:   Custom color selected by Architect.
  590.         4.  Motors and Blower Wheels:  Totally enclosed air over
  591.             (TEAO) type motor(s), suitable for continuous heavy
  592.             duty, all angle operation.
  593. NOTE ** Delete the following paragraph unless explosion
  594.         proof motors are required.
  595.             a.  Explosion proof.
  596.             b.  Sealed lifetime pre-lubricated ball bearings,
  597.                 resilient mounted and protected by an automatic
  598.                 reset thermal overload switch.
  599.             c.  Quick disconnect plugs for fast easy removal of
  600.                 motor/fan assemblies for inspection and cleaning.
  601. NOTE ** Insert information into following paragraph;
  602.         consult manufacturer's product data for specific
  603.         model specifications.
  604.             d.  Double extended shaft and direct drive, double
  605.                 inlet, dynamically balanced forward curved
  606.                 squirrel cage blower wheels having capacity to
  607.                 provide ____ feet per minute (____ m/sec) air
  608.                 velocity and ____ cubic feet per minute (____
  609.                 L/sec) air volume at nozzle.
  610. NOTE ** Delete two of the following three paragraphs;
  611.         consult manufacturer's product data for specific
  612.         model specifications.
  613.             e.  Motor:  Single 1/2 horsepower, maximum 1,750
  614.                 revolutions per minute, single-speed, with two-
  615.                 speed option.
  616.             f.  Motor:  Single 1 horsepower, maximum 1,750
  617.                 revolutions per minute, single-speed, with two-
  618.                 speed option.
  619.             g.  Motor:  Two 1/2 horsepower, maximum 1,750
  620.                 revolutions per minute, single-speed, with two-
  621.                 speed option, both controlled by single switch.
  622. NOTE ** Insert information into following paragraph;
  623.         consult manufacturer's product data for specific
  624.         model specifications.
  625.         5.  Utility Requirements:  ___ Volts AC, ______-phase,
  626.             ___ Ampere(s).
  627. NOTE ** Delete one of the following two paragraphs.
  628.         Junction box mounted on right side is standard;
  629.         complete the second paragraph if an alternative
  630.         mounting is required.
  631.         6.  Electrical Wiring:  Junction box mounted on right
  632.             side.
  633.         7.  Electrical Wiring:  Junction box mounted ___________.
  634. NOTE ** Retain following paragraph if specifying unit with
  635.         optional door-activated microswitch(s).
  636.         8.  Door-Activated Microswitch(s):  Supply 20 amp
  637.             microswitch(s) for automatic on/off control, on when
  638.             door is opened, off when door is closed; field
  639.             installed.
  640. NOTE ** Delete one of the following two paragraphs.
  641.         Plunger type is for doors with hinges (swing
  642.         doors), roller type for all other types of doors.
  643.             a.  Type:  Plunger.
  644.             b.  Type:  Roller.
  645. NOTE ** Mars recommends the use of a motor control panel on
  646.         three phase motors whenever a door microswitch is
  647.         used to start and stop the air curtain.  One door
  648.         microswitch is used to directly control one or two
  649.         1/2 HP single phase motors without the need for a
  650.         motor control panel.  If a motor control panel is
  651.         required, select one of the following two
  652.         paragraphs and indicate the total number of motors
  653.         (1, 2, 3, or 4) to be powered through the panel.
  654.         9.  Wall Mounted Control Panel:  Power ___ motors through
  655.             the panel.
  656.         10. Factory Mounted Control Panel on Air Curtain:  Power
  657.             ___ motors through the panel.
  658. NOTE ** Insert information into following paragraph;
  659.         consult manufacturer's product data for specific
  660.         model specifications.
  661.         11. Operating Noise Level:  __ decibels on A scale,
  662.             measured from interior, 10 feet (3.048 m) from unit.
  663. NOTE ** Retain following paragraph if specifying Mars Super
  664.         COMBI units.  These units utilize 1 horsepower
  665.         motors and provide up to 4,600 FPM (23 m/sec) at
  666.         the nozzle.  They are available unheated only and
  667.         can be used for the same purposes as CHS models.
  668.  
  669.     G.  Air Curtains:
  670. NOTE ** Insert Model Number information in following
  671.         paragraph.
  672.         1.  Acceptable Product:  Mars Model Number ____ Super
  673.             COMBI.
  674.         2.  Product Description:  Self-contained electrically-
  675.             operated air curtain for mounting at head of openings
  676.             up to 12 feet (3.658 m) high.
  677.         3.  Housing:
  678.             a.  One piece molded white high-impact polyethylene
  679.                 material, resistant to high humidity and all
  680.                 climatic conditions.
  681.             b.  Internal steel bracket with sufficient strength
  682.                 to provide housing rigidity and fastening to
  683.                 wall.
  684.             c.  Mechanically field adjustable variable air intake
  685.                 louver assembly capable of reducing outlet air
  686.                 velocity up to 60 percent with louvers in totally
  687.                 enclosed position.
  688.             d.  Wedge shaped discharge air outlet nozzle
  689.                 containing adjustable air directional vanes with
  690.                 a +/- 20 degree sweep from front to back.
  691. NOTE ** Delete all but one of the following subparagraphs.
  692.         White is standard; custom colors available.
  693.             e.  Color:   White.
  694.             f.  Color:   Gray.
  695.             g.  Color:   Gold.
  696.             h.  Color:   Beige.
  697.             i.  Color:   Dark Bronze.
  698.             j.  Color:   Custom color selected by Architect.
  699. NOTE ** Insert information into following paragraph;
  700.         consult manufacturer's product data for specific
  701.         model specifications.
  702.         4.  Blower Assembly:  Direct-drive, double-width and
  703.             double-inlet squirrel cage steel blower wheels having
  704.             capacity to provide ____ feet per minute (____ m/sec)
  705.             air velocity and ____ cubic feet per minute (____
  706.             L/sec) air volume at nozzle.
  707. NOTE ** Delete one of the following two paragraphs; consult
  708.         manufacturer's product data for specific model
  709.         specifications.
  710.         5.  Motor:  Single 1 horsepower, two-speed, with two-
  711.             speed on/off control switch; single phase only.
  712.         6.  Motor:  Two 1 horsepower, two-speed, both controlled
  713.             by single two-speed on/off control switch; single
  714.             phase only.
  715. NOTE ** Retain following paragraph if specifying unit with
  716.         optional door-activated microswitch.
  717.         7.  Door-Activated Microswitch:  Supply microswitch for
  718.             automatic on/off control, on when door is opened, off
  719.             when door is closed; field installed.
  720. NOTE ** Delete one of the following two paragraphs.
  721.         Plunger type is for doors with hinges (swing
  722.         doors), roller type for all other types of doors.
  723.             a.  Type:  Plunger.
  724.             b.  Type:  Roller.
  725. NOTE ** Insert information into following paragraph;
  726.         consult manufacturer's product data for specific
  727.         model specifications.
  728.         8.  Operating Noise Level:  __ decibels on A scale,
  729.             measured from interior, 10 feet (3.048 m) from unit.
  730. NOTE ** Insert information into following paragraph;
  731.         consult manufacturer's product data for specific
  732.         model specifications.
  733.         9.  Utility Requirements:  ___ Volts AC, ______-phase,
  734.             ___ Ampere(s).
  735. NOTE ** Retain following paragraph if specifying Mars
  736.         HEPAC(R) unit Model HF40.  HEPAC(R) air curtains
  737.         contain a pre-filter and HEPA filter that is rated
  738.         at 99.97 percent efficiency at removing airborne
  739.         particle down to 0.3 microns, including dust,
  740.         bacteria, molds, pollens, and tobacco smoke.
  741. NOTE **
  742. NOTE ** Mars HEPAC(R) units are supplied with electrical
  743.         cord and standard wall outlet plug; they can also
  744.         be used in portable bench top operations and are
  745.         effective when placed adjacent to critical work
  746.         areas.
  747. NOTE **
  748. NOTE ** To be mounted inside building only, their typical
  749.         use is over an entrance to a cleanroom.
  750.  
  751.     H.  High Efficiency Particulate Air Curtain (HEPAC(R)):
  752.         1.  Acceptable Product:  Mars Model Number HF40.
  753.         2.  Product Description:  Self-contained electrically-
  754.             operated air curtain for mounting at head of openings
  755.             up to 8 feet (2.438 m) high.
  756.         3.  Housing:
  757.             a.  One piece molded white high-impact polyethylene
  758.                 material, resistant to high humidity and all
  759.                 climatic conditions.
  760.             b.  Internal steel bracket with sufficient strength
  761.                 to provide housing rigidity and fastening to
  762.                 wall.
  763.             c.  Mechanically field adjustable variable air intake
  764.                 louver assembly capable of reducing outlet air
  765.                 velocity up to 60 percent with louvers in totally
  766.                 enclosed position.
  767.             d.  Wedge shaped discharge air outlet nozzle
  768.                 containing adjustable air directional vanes with
  769.                 a +/- 20 degree sweep from front to back.
  770. NOTE ** Delete one of the following two paragraphs. White
  771.         is production color; custom colors available.
  772.             e.  Color:   White.
  773.             f.  Color:   Custom color selected by Architect.
  774.         4.  Blower Assembly:  Direct-drive, double-width and
  775.             double-inlet squirrel cage steel blower wheels having
  776.             capacity to provide ____ feet per minute (____ m/sec)
  777.             air velocity and ____ cubic feet per minute (____
  778.             L/sec) air volume at nozzle.
  779. NOTE ** Insert information into following paragraph;
  780.         consult manufacturer's product data for specific
  781.         model specifications.
  782.         5.  Utility Requirements:  1/2 horsepower motor, ___
  783.             Volts AC, ______-phase, ___ Ampere(s).
  784.  
  785.     I.  Fastening Devices:  Types recommended in manufacturer's
  786.         printed installation instructions for indicated
  787.         substrates.
  788.  
  789.  
  790. PART 3  EXECUTION
  791.  
  792. 3.1 EXAMINATION
  793.  
  794.     A.  Verify that required utilities are in correct location
  795.         and are of correct capacities for specified products.
  796.  
  797. 3.2 INSTALLATION
  798.  
  799.     A.  Install air curtains in accordance with shop drawings and
  800.         manufacturer's printed installation instructions.
  801.  
  802.     B.  Connection to utilities is specified in Sections of
  803.         Division 16.
  804.  
  805.  
  806.                          END OF SECTION
  807.